Application
Application | short-circuit monitoring; Wire break monitoring |
Electrical data
Operating voltage tolerance [%] | -15...25 |
Operating voltage [V] | 24 DC |
Current consumption [mA] | < 50 |
Number of channels | 2 |
Outputs
Electrical design | Relay; (per channel: 1 changeover contact configurable) |
Contact rating | 253 V AC / 2 A / cos phi > 0,7 // 40 V DC / 2 A; (resistive load) |
Switching frequency DC [Hz] | 10 |
Operating conditions
Ambient temperature [°C] | -20...60 |
Protection | IP 20 |
Tests / approvals
Approval | PTB 02 ATEX 2036; IECEx PTB 17.0024 |
ATEX marking | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC |
EMC | EN 50081-2 | (1993) | EN 61326-1 | (2006) | |
MTTF [years] | 325 |
Mechanical data
Weight [g] | 188.45 |
Switching cycles mechanical | 10 million |
Displays / operating elements
Display | Switching status | 2 x LED, yellow | Power | LED, green | Function | 2 x LED, red | |
Remarks
Remarks | Caution The control monitor must be mounted outside the hazardous area. | Free terminals must not be used. | |
Pack quantity | 1 pcs. |
Electrical connection
Connection | terminals: ...2.5 mm² |
Other data
Maximum values for control circuit
in protection rating intrinsic safety | [EEx ia] IIC | [EEx ia] IIB | [EEx ib] IIC | [EEx ib] IIB |
Voltage [V] | 10.5 | 10.5 | 10.5 | 10.5 |
Current [mA] | 13 | 13 | 13 | 13 |
Power [mW] | 34 | 34 | 34 | 34 |
External inductance [mH] | 210 | 840 | 210 | 840 |
External capacitance [µF] | 2.41 | 16.8 | 2.41 | 16.8 |