Add to Cart
Electronic pressure monitor | |||||||||
M12 connector | |||||||||
Function programmable | |||||||||
Measuring element: ceramic-capacitive pressure measuring cell | |||||||||
Process connection: G ¼ I | |||||||||
2 outputs OUT1 = switching output OUT2 = switching output | |||||||||
4-digit alphanumeric display / alternating indication of red and green | |||||||||
Measuring range: -1...10 bar / -14.5...145 psi / -0.1...1.0 MPa | |||||||||
Application | |||||||||
Application | Type of pressure: relative pressure | ||||||||
liquids and gases of the fluid group 2 according to Article 9 of the Pressure Equipment | |||||||||
Directive (PED) | |||||||||
For gas applications > 25 bar: select PN7x7x series | |||||||||
Pressure rating | 75 bar 1087 psi 7.5 MPa | ||||||||
Bursting pressure min. | 150 bar 2175 psi 15 MPa | ||||||||
Medium temperature | [°C] | -25...80 | |||||||
Electrical data | |||||||||
Electrical design | DC PNP/NPN | ||||||||
Operating voltage | [V] | 18...30 DC ¹) | |||||||
Current consumption | [mA] | < 35 | |||||||
Insulation resistance | [MΩ] | > 100 (500 V DC) | |||||||
Protection class | III | ||||||||
Reverse polarity protection | yes | ||||||||
Outputs | |||||||||
Output | 2 outputs | ||||||||
OUT1 = switching output | |||||||||
OUT2 = switching output | |||||||||
Output function | 2 x normally open / closed programmable | ||||||||
PN7094 | |||||||||
PN-010-RER14-QFRKG/US/ /V Pressure sensors | |||||||||
Current rating | [mA] | 150; 200 (...60 °C); 250 (...40 °C) | |||||||
Voltage drop | [V] | < 2.5 | |||||||
Short-circuit protection | pulsed | ||||||||
Overload protection | yes | ||||||||
Switching frequency | [Hz] | ≤ 170 | |||||||
Measuring / setting range | |||||||||
Measuring range -1...10 bar -14.5...145 psi -0.1...1.0 MPa Setting range | |||||||||
Set point, SP -0.90...10 bar -13.5...145 psi -0.09...1 MPa Reset point, rP -0.95...9.95 bar -14...144.5 psi -0.095...0.995 MPa insteps of 0.05 bar 0.5 psi 0.005 MPa | |||||||||
Accuracy / deviations | |||||||||
Accuracy / deviations | |||||||||
(in % of the span) | |||||||||
Switch point accuracy | < ± 0.5 | ||||||||
Characteristics deviation *) | < ± 0.25 (BFSL) / < ± 0.5 (LS) | ||||||||
Hysteresis | < ± 0.25 | ||||||||
Repeatability **) | < ± 0.1 | ||||||||
Long-term stability ***) | < ± 0.05 | ||||||||
Temperature coefficients (TEMPCO) in the temperature range -25...80° C (in % of the span per 10 K) | |||||||||
Greatest TEMPCO of the zero point | 0.2 | ||||||||
Greatest TEMPCO of the span | 0.2 | ||||||||
Reaction times | |||||||||
Power-on delay time [s] | < 0.3 | ||||||||
Min. response time switching | [ms] | < 3 | |||||||
output | |||||||||
Delay time programmable dS, dr [s] | 0...50 | ||||||||
Integrated watchdog | yes | ||||||||
Software / programming | |||||||||
Programming options | hysteresis / window function; NO / NC; output polarity; on delay, off delay; damping; display unit | ||||||||
Interfaces | |||||||||
IO-Link device | |||||||||
Transfer type | COM2 (38.4 kBaud) | ||||||||
IO-Link revision | 1.1 | ||||||||
SDCI standard | IEC 61131-9 | ||||||||
IO-Link device ID | 403 d / 00 01 93 h | ||||||||
Profiles | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis | ||||||||
SIO mode | yes | ||||||||
Required master port class | A | ||||||||
Process data analogue | 1 | ||||||||
Process data binary | 2 | ||||||||
Min. process cycle time [ms] | 2.3 | ||||||||
Environment | |||||||||
Ambient temperature [°C] Storage temperature [°C] | -25...80 | ||||||||
-40...100 | |||||||||
PN7094 | |||||||||
PN-010-RER14-QFRKG/US/ /V Pressure sensors | |||||||||
Protection IP 65 / IP 67 | |||||||||
Tests / approvals | |||||||||
Pressure equipment directive | Sound | engineering practice | |||||||
EMC | DIN EN 61000-6-2 | ||||||||
DIN EN 61000-6-3 | |||||||||
Shock resistance | DIN EN 60068-2-27 | 50 g (11 ms) | |||||||
Vibration resistance | DIN EN 60068-2-6 | 20 g (10...2000 Hz) | |||||||
MTTF [Years] | 224.01 | ||||||||
UL approval number | J001 | ||||||||
Mechanical data | |||||||||
Process connection | G ¼ I | ||||||||
Materials (wetted parts) | 1.4404; ceramics; FKM | ||||||||
Housing materials | 1.4404; PBT+PC-GF 30; PBT-GF 20; PC | ||||||||
Switching cycles min. | 100 million | ||||||||
Tightening torque [Nm] | 25...35 (recommended tightening torque²) | ||||||||
Weight [kg] | 0.234 | ||||||||
Displays / operating elements | |||||||||
Display | Display unit 3 x LED green (bar, psi, MPa) Switching status 2 x LED yellow 4-digit alphanumeric display / alternating indication Measured values of red and green | ||||||||
Electrical connection | |||||||||
Connection M12 connector; Gold-plated contacts | |||||||||
Wiring | |||||||||
Core colours | |||||||||
BK | black | ||||||||
BN | brown | ||||||||
BU | blue | ||||||||
WH | white | ||||||||
OUT1: switching output or IO-Link | |||||||||
OUT2: switching output | |||||||||
Colours to DIN EN 60947-5-2 | |||||||||
Remarks | |||||||||
Remarks | ¹) to EN50178, SELV, PELV | ||||||||
*) BFSL = Best Fit Straight Line / LS = Limit Value Setting **) with temperature fluctuations < 10 K ***) in% of the span / 6 months | |||||||||
²) Depends on lubrication, sealand pressure rating | |||||||||
Pack quantity [piece] | 1 |