Add to Cart
Technical Features
Category
|
Details
|
General Information
|
|
- Material Number
|
X20AI8321
|
- Brand
|
B&R
|
- Product Type
|
Analog Input Module
|
- Function
|
Receive and convert analog current signals to digital values for industrial control systems
|
- B&R ID Code
|
0xD831
|
- Warranty
|
Usually 12 months (varies by region and distributor)
|
- Status Indicators
|
I/O function per channel, operating state, module status
|
- Diagnostics
|
Module run/error and input diagnostics available via LED status indicators and software
|
- Power Consumption
|
Bus: 0.01 W; Internal I/O: 1.37 W (rev. ≥ D0), 1.24 W (rev. < D0)
|
Input Specifications
|
|
- Number of Inputs
|
8
|
- Input Type
|
Differential analog input
|
- Input Ranges
|
0 to 20 mA or 4 to 20 mA
|
- Digital Converter Resolution
|
12 - bit
|
- Conversion Time
|
1 ms for all inputs
|
- Output Format (Data Type)
|
int
|
- Current Output Range (Digital Representation)
|
0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 μA
|
- Load
|
< 300 Ω
|
- Input Protection
|
Protection against wiring with supply voltage, reverse polarity protection
|
- Permissible Input Signal
|
Max. ± 50 mA
|
- Output of Digital Value during Overload
|
Configurable
|
- Conversion Procedure
|
SAR (Successive Approximation Register)
|
- Input Filter
|
Third - order low - pass filter / cut - off frequency 1 kHz
|
- Max. Error (Gain)
|
0.08%
|
- Max. Error (Offset)
|
0.03%
|
- Max. Gain Drift
|
0.009%/°C
|
- Max. Offset Drift
|
0.005%/°C
|
- Common - Mode Rejection (DC)
|
70 dB
|
- Common - Mode Rejection (50 Hz)
|
70 dB
|
- Common - Mode Range
|
± 12 V
|
- Crosstalk between Channels
|
- 70 dB
|
- Nonlinearity
|
< 0.05%
|
- Insulation Voltage between Channel and Bus
|
500 VDC, 1 min
|
Electrical Properties
|
|
- Electrical Isolation
|
Channel isolated from bus; channel not isolated from channel
|
Environmental Conditions
|
|
- Mounting Orientation
|
Horizontal and vertical
|
- Installation Elevation above Sea Level
|
0 - 2000 m: no limitation; > 2000 m: reduction of ambient temperature by 0.5 °C per 100 m
|
- Degree of Protection per EN 60529
|
IP20
|
- Temperature (Operation - Horizontal Mounting)
|
- 25 to 60 °C
|
- Temperature (Operation - Vertical Mounting)
|
- 25 to 50 °C
|
- Temperature (Storage)
|
- 40 to 85 °C
|
- Temperature (Transport)
|
- 40 to 85 °C
|
- Relative Humidity (Operation)
|
5 - 95%, non - condensing
|
- Relative Humidity (Storage)
|
5 - 95%, non - condensing
|
- Relative Humidity (Transport)
|
5 - 95%, non - condensing
|
Mechanical Properties
|
|
- Pitch
|
12.5 + 0.2 mm
|
- Mandatory Accessories
|
Bus modules (e.g., X20BM11, X20BM15); Terminal blocks (e.g., X20TB1F)
|
Certifications
|
|
- CE
|
Yes
|
- UKCA
|
Yes
|
- ATEX
|
Zone 2, II 3G Ex nA nC IIA T5 Gc; IP20, Ta (see X20 user's manual); FTZÚ 09 ATEX 0083X
|
- UL
|
cULus E115267 (industrial control equipment)
|
- HazLoc
|
cCSAus 244665 (process control equipment for hazardous locations, Class I, Division 2, Groups ABCD, T5)
|
- DNV
|
Temperature: B(0 - 55 °C); Humidity: B(up to 100%); Vibration: B(4 g); EMC: B(bridge and open deck)
|
- CCS
|
Yes
|
- LR
|
ENV1
|
- KR
|
Yes
|
- ABS
|
Yes
|
- BV
|
EC33B, Temperature: 5 - 55 °C, Vibration: 4 g, EMC: Bridge and open deck
|
- KC
|
Yes
|